Voltage range |
Max current (Amps) at Ambient Temperature |
|||
|---|---|---|---|---|
|
40'C |
50'C |
60'C |
71'C |
|
|
+/-12 |
1.4 |
1.3 |
1.1 |
0.6 |
|
+/-15 |
1.6 |
1.4 |
1.2 |
0.7 |
REGULATED VOLTAGE OUTPUT
(each side)
Regulation...............0.1% line or load with input variations
from 105-132 or 132-105 volts AC and
load variations from no load to full
load. or full load to no load.
Ripple and Noise.........1.5 millivolts rms; 5 millivolts peak
to peak.
Temperature Coefficient..Output change in voltage 0.03%/'C.
Remote Sensing...........Provision is made for remote sensing
to eliminate effect of power output
lead resistance on DC regulation.
OVERSHOOT- No overshoot under conditions of power turn-on, turn-off,
or power failure.
AC INPUT -- 105-132 VAC at 47-440 Hz. Ratings apply for 57-63 Hz; at
47-53 Hz input, delete 40'C current rating. For 63-440 Hz input,
consult factory. For input power see table II.
*With output loaded to full current rating and input voltage 132
Volts AC, 60 Hz.
TRACKING -- Absolute voltage difference between negative and positive
outputs within 2%; 0.2% change for all conditions of line, load
and temperature.
OVERLOAD PROTECTION
Thermal.........................Thermostat, resets automatically
when over temperature condition is
eliminated.
Electrical
External...................Automatic electronic current limit-
ing circuit, limits output current
to a pre-set value less than 125%
of 40'C current rating. Automatic
current limiting protects the load
and power supply when external
overloads and direct shorts occur.
Internal...................Fuses Fl and F2 provide protection
against internal circuit failure.
INPUT AND OUTPUT CONNECTIONS -- Terminal block on rear of chassis.
OPERATING AMBIENT TEMPERATURE RANGE AND DUTY CYCLE -- Continuous duty
from O'C to 71'C ambient.
STORAGE TEMPERATURE -- -55'C to 85'C
(non-operating)
V D C ADJ. CONTROL -- Voltage adjust control permits adjustment of DC
output