Voltage range |
Max current (Amps) at Ambient Temperature |
|||
|---|---|---|---|---|
|
40'C |
50'C |
60'C |
71'C |
|
|
6 +/- 5% |
3.7 |
3.7 |
2.5 |
1.9 |
REGULATED VOLTAGE OUTPUT
Regulation...............0.10 line or load with input variations
from 105-132 or 132-105 volts AC and load
variations from no load to full load or
full load to no load.
Ripple and Noise.........1.5 millivolts rms; 5 millivolts peak to
peak with either positive or negative
terminal grounded.
Temperature Coefficient..Output change in voltage 0.03%/'C.
Remote Programming
External Resistor......Nominal 1000 ohms/volt output.
Programming Voltage....One-to-one voltage change.
Remote Sensing...........Provision is made for remote sensing to
eliminate effect of power output lead re-
sistance on DC regulation.
OVERSHOOT -- No overshoot under conditions of power turn-on, turn-off,
or power failure.
A. C. Input -- 105-132 VAC at 47-440 Hz. Input power: 91 Watts*. For
operation at 47-57 Hz delete 40'C current rating. For 63-440 Hz
consult factory.
*With output loaded to full current rating and input voltage
132 volts AC, 60 Hz.
OVERLOAD PROTECTION
Thermal................Thermal circuit resets automatically when
over-temperature condition is eliminated.
Electrical.............Automatic electronic current limiting cir-
cuit, limits output current to a safe value.
Automatic current limiting protects the load
and power supply when external overloads and
direct shorts occur.
OVERVOLTAGE PROTECTION - Model LXS-A-5-0V includes a fixed built-in
overvoltage protection circuit which prevents damage to the load
caused by excessive power supply output voltage. Overvoltage
protection range varies between 6.2 and 7.4 volts D.C.
INPUT AND OUTPUT CONNECTIONS -- Terminal block of rear of chassis.
OPERATING AMBIENT TEMPERATURE RANGE AND DUTY CYCLE -- Continuous duty
from O'C to 71'C ambient.
STORAGE TEMPERATURE (non-operating) -- -55'C to 85'C
OUTPUT ADJUST CONTROL -- Voltage adjust control permits adjustment of
DC output.
MOUNTING -- Three surfaces each with tapped mounting holes can be util-
ized for mounting this unit. All LXS-A power supplies can be
mounted with Top, Front, or Right Side facing up. Top, Front, or
Right Side must be in a horizontal plane. Refer to figure 10 for
mounting details.
"V" OPTION -- All LXS-A power supplies can be obtained for 205-265 VAC
INPUT or 187-242 VAC INPUT. See nameplate for AC input rating.
See schematic diagram for rewiring of AC input. For operation at
47-57Hz delete 40'C current rating. For 63-440 Hz consult
factory.