LXS-A-6 Low Voltage Power Supply

Voltage range

Max current (Amps) at Ambient Temperature

40'C

50'C

60'C

71'C

6 +/- 5%

3.7

3.7

2.5

1.9

 REGULATED VOLTAGE OUTPUT                                                           
                                                                                   
   Regulation...............0.10 line or load with input variations                 
                                           from 105-132 or 132-105 volts AC and load
                                           variations from no load to full load or
                                           full load to no load.                    
                                                                                   
   Ripple and Noise.........1.5 millivolts rms; 5 millivolts peak to                
                                           peak with either positive or negative
                                           terminal grounded.                       
                                                                                   
   Temperature Coefficient..Output change in voltage 0.03%/'C.                      
   Remote Programming                                                               
       External Resistor......Nominal 1000 ohms/volt output.                        
                                                                                   
       Programming Voltage....One-to-one voltage change.                            
                                                                                   
   Remote Sensing...........Provision is made for remote sensing to                 
                                           eliminate effect of power output  lead re-
                                           sistance on DC regulation.               
                                                                                   
 OVERSHOOT  --  No  overshoot  under  conditions  of  power  turn-on,  turn-off,     
       or power failure.                                                            
                                                                                   
 A.  C.  Input  --  105-132 VAC  at 47-440  Hz.   Input power:  91 Watts*.   For     
       operation  at  47-57  Hz  delete  40'C  current rating.   For  63-440 Hz     
       consult factory.                                                             
                                                                                   
       *With output loaded to full current rating and input voltage                 
         132 volts AC, 60 Hz.                                                       

 OVERLOAD PROTECTION                                                               
    Thermal................Thermal circuit resets automatically when
                                 over-temperature condition is eliminated.
    Electrical.............Automatic  electronic current limiting cir-
                                    cuit, limits output current to a safe value.
                                    Automatic   current limiting protects the load
                                    and power   supply when external overloads and
                                    direct shorts occur.                         
                                                                                  
 OVERVOLTAGE PROTECTION - Model LXS-A-5-0V includes a fixed built-in               
    overvoltage protection circuit which prevents damage to the load               
    caused by excessive power supply output voltage.  Overvoltage                  
    protection range varies between 6.2 and 7.4 volts D.C.                        
                                                                                  
 INPUT AND OUTPUT CONNECTIONS -- Terminal block of rear of chassis.                 
                                                                                  
 OPERATING AMBIENT TEMPERATURE RANGE AND DUTY CYCLE -- Continuous duty              
    from O'C to 71'C ambient.                                                      
                                                                                  
 STORAGE TEMPERATURE (non-operating) --   -55'C to 85'C                             
                                                                                  
 OUTPUT ADJUST CONTROL -- Voltage adjust control permits adjustment of              
    DC output.                                                                     
                                                                                  
                                                                      
                                                                                  
                 
           
               
                                                                                  
 MOUNTING -- Three surfaces each with tapped mounting holes can be util-            
    ized for mounting this unit.  All LXS-A power supplies can be                  
    mounted with Top, Front, or Right Side facing up.  Top, Front, or              
    Right Side must be in a horizontal plane.  Refer to figure 10 for             
    mounting details.                                                              
                                                                                  
 "V" OPTION -- All LXS-A power supplies can be obtained for 205-265 VAC             
    INPUT or 187-242 VAC INPUT. See nameplate for AC input rating.                 
    See schematic diagram for rewiring of AC input. For operation at               
    47-57Hz delete 40'C current rating.  For 63-440 Hz consult                     
    factory.                                                                       